Circuit
Breakers Definition:
A circuit breaker can make or break a circuit either
manually or automatically under all conditions viz., no-load, full-load and
short-circuit conditions. This characteristic of the Circuit Breakers
Definition has made it a very useful equipment for switching and protection of
various parts of the power system.
A Circuit Breakers Definition is a piece of
equipment which can
- make or break a circuit either manually or by remote control under normal conditions
- break a circuit automatically under fault conditions
- make a circuit either manually or by remote control under faith conditions
Thus a circuit breaker incorporates manual (or
remote control) as well as automatic control for switching functions. The
latter control employs relays and operates only under fault conditions.
Operating
Principle:
A Circuit Breakers Definition essentially consists
of fixed and moving contacts, called electrodes. Under normal operating
conditions, these contacts remain closed and will not open automatically until
and unless the system becomes faulty. Of course, the contacts can be opened
manually or by remote control whenever desired. When a fault occurs on any part
of the system, the trip coils of the circuit breaker get energised and the
moving contacts are pulled apart by some mechanism, thus opening the circuit.
When the contacts of a circuit breaker are separated
under fault conditions, an arc is struck between them. The current is thus able
to continue until the discharge ceases. The production of arc not only delays
the current interruption process but it also generates enormous heat which may
cause damage to the system or to the circuit breaker itself. Therefore, the
main problem in a Circuit Breakers Definition into extinguish the arc within
the shortest possible time so that heat generated by it may not reach a
dangerous value.
Arc
Phenomenon:
When a short-circuit occurs, a heavy current flows
through the contacts of the ‘circuit breaker, before they are opened by the
protective system. At the instant when the contacts begin to separate, the
contact area decreases rapidly and large fault current causes increased current
density and hence rise in temperature. The heat produced in the medium between
contacts (usually the medium is oil or air) is sufficient to ionise the air or
vapourise and ionise the oil. The ionised air or vapour acts as conductor and
an arc is struck between the contacts. The p.d. between the contacts is quite
small and is just sufficient to maintain the arc. The arc provides a low
resistance path and consequently the current in the circuit remains
uninterrupted so long as the arc persists.
During the arcing period, the current flowing
between the contacts depends upon the arc resistance. The greater the arc
resistance, the smaller the current that flows between the contacts. The arc
resistance depends upon the following factors :
Degree of ionisation – the arc resistance increases
with the decrease in the number of ionised particles between the contacts.
Length of the arc – the arc resistance increases
with the length of the arc i.e., separation of contacts.
Cross-section of arc – the arc resistance increases
with the decrease in area of X-section of the arc.
Principles
of Arc Extinction:
Before discussing the methods of arc extinction, it
is necessary to examine the factors responsible for the maintenance of arc
between the contacts. These are:
- p.d. between the contacts
- ionised particles between contacts
Taking these in turn,
- When the contacts have a small separation, the p.d. between them is sufficient to maintain the arc. One way to extinguish the arc is to separate the contacts to such a distance that p.d. becomes inadequate to maintain the arc. However, this method is impracticable in high voltage system where a separation of many meters my be required.
- The ionised particles between the contacts tend to maintain the arc. If the arc path is deionised, the arc extinction will be facilitated. This may be achieved by cooling the arc or by bodily removing the ionised particles from the space between the contacts.
Methods
of Arc Extinction:
There are two methods of extinguishing the arc in Circuit
Breakers Definition viz
1.
High resistance method
2.
Low resistance or current zero method
1.
High Resistance Method: In this method, arc resistance is
made to increase with time so that current is reduced to a value insufficient
to maintain the arc. Consequently, the current is interrupted or the arc is
extinguished. The principal disadvantage of this method is that enormous energy
is dissipated in the arc. Therefore, it is employed only in d.c. circuit
breakers and low-capacity a.c. Circuit Breakers Definition.
The
resistance of the arc may be increased by:
- Lengthening the arc: The resistance of the arc is directly proportional to its length. The length of the arc can be increased by increasing the gap between contacts.
- Cooling the arc: Cooling helps in the deionisation of the medium between the contacts. This increases the arc resistance. Efficient cooling may be obtained by a gas blast directed along the arc.
- Reducing X-section of the arc: If the area of X-section of the arc is reduced, the voltage necessary to maintain the arc is increased. In other words, the resistance of the arc path is the cross-section of the arc can be reduced by letting the arc pass through a narrow opening or by having smaller area of contacts.
- Splitting the arc: The resistance of the arc can be increased by splitting the arc into a number of smaller arcs in series. Each one of these arcs experiences the effect of lengthening and cooling. The arc may be split by introducing some conducting plates between the
2.
Low resistance or Current Zero Method: This method is
employed for arc extinction in a.c. circuits only. In this method, arc
resistance is kept low until current is zero where the arc extinguishes
naturally and is prevented from restriking inspite of the rising voltage across
the contacts. All modern high power a.c. circuit breakers employ this method for
arc extinction.
In an a.c. system, current drops to zero after every
half-cycle. At every current zero, the arc extinguishes for a brief moment. Now
the medium between the contacts contains ions and electrons so that it has
small dielectric strength and can be easily broken down by the rising contact
voltage known as restriking voltage. If such a breakdown does occur, the arc
will persist for another half-cycle. If immediately after current zero, the
dielectric strength of the medium between contacts is built up more rapidly
than the voltage across the contacts, the arc fails to restrike and the current
will be interrupted. The rapid increase of dielectric strength of the medium
near current zero can be achieved by:
- causing the ionised particles in the space between contacts to recombine into neutral molecules.
- sweeping the ionised particles away and replacing them by un-ionised particles
Therefore, the real problem in a.c. arc interruption
is to rapidly deionise the medium between contacts as soon as the current
becomes zero so that the rising contact voltage or restriking voltage cannot
breakdown the space between contacts. The de-ionisation of the medium can be
achieved by:
Lengthening
of the Gap: The dielectric strength of the medium
is proportional to the length of the gap between contacts. Therefore, by
opening the contacts rapidly, higher dielectric strength of the medium can be
achieved.
High
Pressure: If the pressure in the vicinity of the arc is
increased, the density of the particles constituting the discharge also
increases. The increased density of particles causes higher rate of
de-ionisation and consequently the dielectric strength of the medium between
contacts is increased.
Cooling:
Natural combination of ionised particles takes place more rapidly if they are
allowed to cool. Therefore, dielectric strength of the medium between the
contacts can be increased by cooling the arc.
Blast
Effect: If the ionised particles between the contacts are
swept away and replaced by unionised particles, the dielectric strength of the
medium can be increased considerably. This may be achieved by a gas blast
directed along the discharge or by forcing oil into the contact space.
Important
Points to be Remember:
The
following are the important terms much used in the circuit breaker analysis:
1.
Arc Voltage: It is the voltage that appears across
the contacts of the circuit breaker during the arcing period.
As soon as the contacts of the circuit breaker
separate, an arc is formed. The voltage that appears across the contacts during
arcing period is called the arc voltage. Its value is low except for the
‘period the fault current is at or near zero current point. At current zero,
the arc voltage rises rapidly to peak value and this peak voltage tends to
maintain the current flow in the form of arc.
2.
Restriking Voltage: It is the transient voltage that
appears across the contacts at or near current zero during arcing period.
At current zero, a high-frequency transient voltage
appears across the contacts and is caused by the rapid distribution of energy
between the magnetic and electric fields associated with the plant and
transmission lines of the system. This transient voltage is known as restriking
voltage (Fig. 19.1). The current interruption in the circuit depends upon this
voltage. If the restriking voltage rises more rapidly than the dielectric
strength of the medium between the contacts, the arc will persist for another
half-cycle. On the other hand, if the dielectric strength of the medium builds
up more rapidly than the restriking voltage, the arc fails to restrike and the
current will be interrupted.
3.
Recovery Voltage: It is the normal frequency (50 Hz)
r.m.s. voltage that appears across the contacts of the circuit breaker after
final arc extinction. It is approximately equal to the system voltage.
When contacts of circuit breaker are opened, current
drops to zero after every half cycle. At some current zero, the contacts are
separated sufficiently apart and dielectric strength of the medium between the
contacts attains a high value due to the removal of ionised particles. At such
an instant, the medium between the contacts is strong enough to prevent the
breakdown by the restriking voltage. Consequently, the final arc extinction
takes place and circuit current is interrupted. Immediately after final current
interruption, the voltage that appears across the contacts has a transient part
(See Fig. 19.1). However, these transient oscillations subside rapidly due to
the damping effect of system resistance and normal circuit voltage appears
across the contacts. The voltage across the contacts is of normal frequency and
is known as recovery voltage.